  1.                          SECTION 07411
  2.  
  3.                        METAL ROOF PANELS
  4. NOTE ** Metal panel roofing systems of U.S. Steel
  5.         ACRYLUME(R) steel sheet.
  6. NOTE **
  7. NOTE ** This section is based on metal roof panels made of
  8.         ACRYLUME(R) steel sheet, which is manufactured by
  9.         U.S. Steel Group, a unit of USX Corporation,
  10.         located at the following address:
  11. NOTE **     600 Grant Street
  12. NOTE **     Pittsburgh PA 15219
  13. NOTE **     Tel. (412) 433-1121
  14. NOTE **
  15. NOTE ** ACRYLUME(R) steel does not require painting or
  16.         coating other than the acrylic coating applied
  17.         after milling, nor is it intended for painting on
  18.         continuous coil coating paint lines.
  19. NOTE **
  20. NOTE ** SECTION 07411 - METAL ROOF PANELS, Copyright 1997,
  21.         The Architect's Catalog, Inc.
  22.  
  23.  
  24. PART 1  GENERAL
  25.  
  26. 1.1 SECTION INCLUDES
  27. NOTE ** Delete items below not required for project.
  28.  
  29.     A.  Metal Panel Roof System.
  30.  
  31.     B.  Trim.
  32.  
  33. 1.2 RELATED SECTIONS
  34.  
  35.     A.  Section 07210 - Roof Insulation.
  36.  
  37.     B.  Section 07620 - Sheet Metal Flashing and Trim.
  38.  
  39.     C.  Section 07720 - Roof Accessories.
  40.  
  41.     D.  Section 07900 - Joint Sealants.
  42.  
  43. 1.3 REFERENCES
  44.  
  45.     A.  ASTM A 792/A 792M - Standard Specification for Steel
  46.         Sheet, 55% Aluminum-Zinc Alloy Coated by the Hot Dip
  47.         Process.
  48.  
  49. 1.4 SYSTEM DESCRIPTION
  50.  
  51.     A.  Design Requirements:
  52. NOTE ** Retain the following two sub-paragraphs if
  53.         performance specifying a Contractor-designed
  54.         system, inserting project requirements; delete if
  55.         structural design of system is in Contract
  56.         Documents.
  57.         1.  Vertical loads:  Roof panel system to withstand loads
  58.             imposed by roof panel system, and live loading of __
  59.             pounds per square foot (___ kg/sq m), uniformly
  60.             distributed.
  61.         2.  Snow loads:  Roof panel system to withstand snow
  62.             loads in accordance with requirements of local
  63.             authorities having jurisdiction; imposed snow load is
  64.             to be added to specified vertical loads when
  65.             designing roof panel system.
  66. NOTE ** Insert wind uplift resistance requirements in the
  67.         following sub-paragraph.
  68.         3.  Wind uplift:  Roofing panel system, including panels,
  69.             clips, and fasteners to meet requirements of UL Class
  70.             __ for indicated exposure.
  71.         4.  Expansion/Contraction:  Roof panel system to include
  72.             provision for structural and thermal movement without
  73.             loss of water resistance integrity.
  74.  
  75. 1.5 SUBMITTALS
  76.  
  77.     A.  Submit under provisions of Section 01300.
  78.  
  79.     B.  Product Data:  Manufacturer's descriptive literature for
  80.         roof panel system, including each specified component.
  81.  
  82.     C.  Shop Drawings:
  83.         1.  Roof plans:  Dimensioned drawings indicating the
  84.             following:
  85.             a.  Layout of roof panels; include fastener
  86.                 locations.
  87.             b.  Locations of trim and other sheet metal items.
  88.         2.  Details:  Dimensioned drawings indicating the
  89.             following:
  90.             a.  Profile of each type trim and other sheet metal
  91.                 item.
  92.             b.  Interface of roof panel system with adjacent
  93.                 construction.
  94.             c.  Illustration of each type fastener.
  95.  
  96.     D.  Quality Assurance Submittals:
  97. NOTE ** Retain the following sub-paragraph if performance
  98.         specifying a Contractor-designed system; delete if
  99.         structural design of system is in Contract
  100.         Documents.
  101.         1.  Design data:  Structural design calculations, bearing
  102.             seal and signature of professional structural
  103.             engineer licensed to practice in the State in which
  104.             the project is located.
  105.         2.  Test reports:  Certified reports documenting testing
  106.             and compliance of roof panel system, as designed, to
  107.             requirements of specified wind uplift requirements.
  108.         3.  Certificates:  Contractor's certification that:
  109.             a.  Manufacturer of roof panel system meets specified
  110.                 qualifications.
  111.             b.  Installer of roof panel system meets specified
  112.                 qualifications.
  113.         4.  Manufacturer's instructions:  Printed installation
  114.             instructions for each roof panel system component,
  115.             including product storage requirements.
  116.  
  117.     E.  Closeout Submittals:  Warranty documents specified in
  118.         WARRANTY Article of PART 1 of this section.
  119.  
  120. 1.6 QUALITY ASSURANCE
  121. NOTE ** Insert qualifications requirements in the following
  122.         paragraph.
  123.  
  124.     A.  Qualifications:
  125.         1.  Manufacturer:  Minimum ___ years documented
  126.             experience producing roof panel systems similar to
  127.             that specified in this section.
  128.         2.  Installer:  Minimum ___ years documented experience
  129.             installing roof panel systems similar to that
  130.             specified in this section.
  131.  
  132. NOTE ** Delete the following paragraph if not required.
  133.  
  134.     B.  Pre-Installation Meetings:
  135.         1.  Convene at job site seven (7) calendar days prior to
  136.             scheduled beginning of construction activities of
  137.             this section to review requirements of this section.
  138.         2.  Require attendance by representatives of the
  139.             following:
  140.             a.  Installer of this section.
  141.             b.  Other entities directly affecting, or affected
  142.                 by, construction activities of this section.
  143.         3.  Notify Architect four (4) calendar days in advance of
  144.             scheduled meeting date.
  145.  
  146. 1.7 DELIVERY, STORAGE, AND HANDLING
  147.  
  148.     A.  Store products of this section in manufacturer's unopened
  149.         packaging until installation.
  150.  
  151.     B.  Maintain storage area conditions for products of this
  152.         section in accordance with manufacturer's instructions
  153.         until installation:
  154.         1.  Store products above ground on elevated platforms;
  155.             incline platforms for moisture run-off.
  156.         2.  Ventilate between individual products to prevent
  157.             moisture condensation build-up.
  158.  
  159. 1.8 PROJECT/SITE CONDITIONS
  160.  
  161.     A.  Field Measurements:  When construction schedule permits,
  162.         take field measurements of areas to receive roof panel
  163.         system; indicate measurements on submitted shop drawings,
  164.         noting discrepancies.
  165.  
  166. 1.9 WARRANTY
  167. NOTE ** The following paragraph specifies a specimen
  168.         Special Warranty.  If retained, edit for project
  169.         requirements and coordinate with General Conditions
  170.         and Division 1; if combined warranty for
  171.         construction activities of other sections is
  172.         required, edit list in third paragraph and
  173.         coordinate with RELATED SECTIONS Article of this
  174.         section.
  175.  
  176.     A.  Special Warranty:
  177.         1.  The Contractor warrants construction activities of
  178.             this section, as installed, to be in accordance with
  179.             the Contract Documents and to be free from faults and
  180.             defects in materials and workmanship for a period of
  181.             three (3) years.
  182.         2.  Have warranty countersigned by representatives of
  183.             manufacturer and installer of this section.
  184. NOTE ** Delete the following two sub-paragraphs if combined
  185.         special warranty not required.
  186.         3.  Combine special warranty of this section with
  187.             construction activities, as installed, of the
  188.             following sections:
  189.             a.  Section 07210 - Roof Insulation.
  190.             b.  Section 07620 - Sheet Metal Flashing and Trim.
  191.             c.  Section 07720 - Roof Accessories.
  192.             d.  Section 07900 - Joint Sealants.
  193.         4.  Have special warranty countersigned by
  194.             representatives of installers of other sections
  195.             affected by combined special warranty.
  196.  
  197.     B.  Manufacturer's Warranty:  Manufacturer's warranty against
  198.         failure of roof panel due to rupture, structural failure,
  199.         or perforation due to exposure to normal atmospheric
  200.         corrosion; warranty period 20 years and 6 months.
  201.  
  202.  
  203. PART 2  PRODUCTS
  204.  
  205. 2.1 MANUFACTURERS
  206. NOTE ** Consult manufacturer of metal material for listing
  207.         of roof panel manufacturers nearest project
  208.         location.
  209.  
  210.     A.  Acceptable Manufacturers:  One of the following:
  211.         1.  _______________.
  212.         2.  _______________.
  213.         3.  _______________.
  214. NOTE ** Delete one of the two following paragraphs;
  215.         coordinate with Division 1 requirements.
  216.  
  217.     B.  Requests for substitution will be considered in
  218.         accordance with provisions of Section 01600.
  219.  
  220.     C.  Substitutions:  Not permitted.
  221.  
  222. 2.2 MATERIALS
  223.  
  224.     A.  Coated Steel Sheet:
  225.         1.  Acceptable material:  ACRYLUME(R), manufactured by
  226.             U.S. Steel Group, a unit of USX Corporation; 600
  227.             Grant Street, Pittsburgh PA 15219;. ASD. Tel. (412)
  228.             433-1121.
  229.         2.  Characteristics:  Aluminum-zinc alloy-coated steel
  230.             sheet conforming to ASTM A 792/A 792M,Coating
  231.             Designation AZ55 (AZ 165), Structural Quality (SQ),
  232.             with clear acrylic coating both faces.
  233.  
  234. 2.3 COMPONENTS
  235. NOTE ** Review the following paragraphs in this Article;
  236.         delete paragraphs specifying components not
  237.         applicable to project.
  238.  
  239.     A.  Roof Panels:
  240. NOTE ** Retain the following sub-paragraphs to specify
  241.         manufacturers' product designations.
  242.         1.  Acceptable products:  One of the following:
  243.             a.  _______________.
  244.             b.  _______________.
  245.             c.  _______________.
  246. NOTE ** Retain one of the following two sub-paragraphs to
  247.         specify profile required for project; if second is
  248.         retained, insert selected panel manufacturers'
  249.         profile designations.
  250.         2.  Profiles:  Indicated on drawings.
  251.         3.  Profile:  One of the following:
  252.             a.  _______________.
  253.             b.  _______________.
  254.             c.  _______________.
  255. NOTE ** Retain one of the following six sub-paragraphs to
  256.         specify structural grade required for project.
  257.         4.  Material:  Coated steel sheet, Grade 33 (230).
  258.         5.  Material:  Coated steel sheet, Grade 37 (255).
  259.         6.  Material:  Coated steel sheet, Grade 40 (275).
  260.         7.  Material:  Coated steel sheet, Grade 50A (345A).
  261.         8.  Material:  Coated steel sheet, Grade 50B (345B).
  262.         9.  Material:  Coated steel sheet, Grade 80 (550).
  263. NOTE ** Insert metal thickness requirement in the following
  264.         sub-paragraph.
  265.         10. Metal thickness:  __ gage (__ mm).
  266.  
  267.     B.  Panel Clips:  Manufacturer's standard for roof panel
  268.         system and specified wind uplift resistance requirements.
  269.  
  270.     C.  Roof Insulation:  Specified in Section 07210.
  271.  
  272.     D.  Roof Accessories:  Specified in Section 07720.
  273.  
  274.     E.  Trim:
  275.         1.  Trim for indicated project conditions includes both
  276.             manufacturer's standard trim profiles and site-formed
  277.             sheet metal items that are not manufacturer's
  278.             standard trim profiles, and includes, but is not
  279.             limited to, the following:
  280.             a.  Fascia.
  281.             b.  Closures.
  282.             c.  Panel terminations.
  283.             d.  Perimeter and termination flashings.
  284.         2.  Material:  Coated steel sheet, Grade 33 (230).
  285. NOTE ** Insert metal thickness requirement in the following
  286.         sub-paragraph.
  287.         3.  Metal thickness:  __ gage (__ mm).
  288.  
  289.     F.  Joint Sealants:  Specified in Section 07900; type
  290.         recommended in manufacturer's instructions for indicated
  291.         use.
  292.  
  293.     G.  Fasteners:
  294.         1.  For panel clips:  Non-corroding fasteners of types
  295.             specified by roof panel system manufacturer for
  296.             indicated substrates and specified wind uplift
  297.             resistance requirements.
  298.         2.  For metal trim and roof penetration devices:  Non-
  299.             corroding die-cast head steel screws, aluminum-zinc
  300.             alloy-coated, with weathersealing washers.
  301.  
  302. 2.4 FABRICATION
  303.  
  304.     A.  Fabricate indicated site-formed metal items to roof panel
  305.         manufacturer's specifications for factory-formed trim in
  306.         accordance with Architect-accepted shop drawings.
  307.  
  308.  
  309. PART 3  EXECUTION
  310.  
  311. 3.1 EXAMINATION
  312.  
  313.     A.  Verification of Conditions:
  314.         1.  Substrate is ready to receive roof panel system.
  315.         2.  Roof penetrations are completed.
  316.  
  317.     B.  Installer's Examination:
  318.         1.  Have installer of this section examine conditions
  319.             under which construction activities of this section
  320.             are to be performed, then submit written notification
  321.             if such conditions are unacceptable.
  322.         2.  Transmit two copies of installer's report to
  323.             Architect within 24 hours of receipt.
  324.         3.  Beginning construction activities of this section
  325.             before unacceptable conditions have been corrected is
  326.             prohibited.
  327.         4.  Beginning construction activities of this section
  328.             indicates installer's acceptance of conditions.
  329.  
  330. 3.2 INSTALLATION
  331.  
  332.     A.  Install roof panel system components in accordance with
  333.         Architect-accepted shop drawings, and manufacturer's
  334.         instructions.
  335.  
  336.     B.  Installation of roof insulation is specified in Section
  337.         07210.
  338.  
  339.     C.  Installation of trim is specified in Section 07620.
  340.  
  341.     D.  Installation of roof accessories is specified in Section
  342.         07720.
  343.  
  344.     E.  Installation of joint sealants is specified in Section
  345.         07900.
  346.  
  347. 3.3 PROTECTION
  348.  
  349.     A.  Protect installed products from damage by subsequent
  350.         construction activities.
  351.  
  352.     B.  Replace products having damage which cannot be repaired
  353.         to Architect's acceptance.